Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 12:21 PM
  • 18 0129_18 0128 _05012018_042211.mp4

Date
01/05/2018
W/O
679305
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13950
Time
4:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5305
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_679305_TV18170_JAN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0129
Downstream MH
18 0128
Dir. of Survey
Downstream
Length Surveyed
17.1 ft.
Total Length
17.2 ft.
Structural Index
4
Structural Quick
5333
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
24
Pipe schematic from manhole 18 0129 to 18 0128
MH: 18 0129MH: 18 0128downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01292.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start17 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish17.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish17.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK17.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0128

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
17SAP
17.2SRV
2.1SAP
0MWL
0MWM
17.2MGOCONNECTION AT MH 3 O'CLOCK
0AMH18 0129
17.2AMH18 0128
4.6SRV

Properties (6)

additional_info
SC346779
custom_field_two
2
customer
LACSD
datetime
2018-01-05T04:21:18-08:00
documentation
PROPIPE
is_lateral_inspection
false