Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 12:19 PM
  • 03 0060_03 0059_1252018_052936.mp4

Date
01/25/2018
W/O
0686418
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00366
PipeID
P05081
Time
4:19 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0731
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
ARTESIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
09
Purpose
Maintenance Related
Project
20180125MDM_LOS_COYOTES_DIAGONAL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
03 0060
Downstream MH
03 0059
Dir. of Survey
Downstream
Length Surveyed
308.8 ft.
Total Length
308.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 03 0060 to 03 0059
MH: 03 0060MH: 03 0059downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:25AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE4.7 ft. MGO - General Observation - 15" VCP39.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active90.7 ft. DAE - Deposits Attached Encrustation, 10 % TO 20% of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES - THROUGHOUT REACH144.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active199.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active232.9 ft. MWM - Water Mark, 30 %of cross sectional area232.9 ft. MWL - Water Level, 20 %of cross sectional area281.8 ft. MWL - Water Level, 40 %of cross sectional area281.8 ft. MWM - Water Mark, 50 %of cross sectional area300.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active308.4 ft. MGO - General Observation - MH CONN ACTIVE 9:00308.8 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (2)

  • General Observation - 15" VCP

    4.7 ft. - General Observation - 15" VCP

  • Deposits Attached Encrustation, 10 % TO 20% of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES - THROUGHOUT REACH

    90.7 ft. - Deposits Attached Encrustation, 10 % TO 20% of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES - THROUGHOUT REACH

Observations (16)

DistanceCodeObservation
232.9MWM
4.7MGO15" VCP
0AMH5:25AM
39.3TFActive
0MWM
0MWL
232.9MWL
308.4MGOMH CONN ACTIVE 9:00
281.8MWL
144.1TFActive
90.7DAETHROUGHOUT REACH
199.9TFActive
281.8MWM
300.4TFActive
308.8AMH5:45AM
0MGOMH CONN 9:00 ACTIVE

Properties (4)

customer
LACSD
datetime
2018-01-25T04:19:57-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false