Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2018, 12:03 PM
  • 08 0131_08 0130_5302018_051024.mp4

Date
05/30/2018
W/O
0706725
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00187
Time
5:03 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0874
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
08_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0131
Downstream MH
08 0130
Dir. of Survey
Downstream
Length Surveyed
275 ft.
Total Length
275 ft.
Structural Index
2
Structural Quick
3129
Structural Rating
21
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 08 0131 to 08 0130
MH: 08 0131MH: 08 0130downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM0 ft. MWL - Water Level, 5 %of cross sectional area - NO FLOW0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped8 ft. MGO - General Observation - 12" VCP18 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT42.2 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL59.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active65.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H81.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL110.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped120.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL136.7 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SL136.7 ft. MWL - Water Level, 10 %of cross sectional area - NO FLOW161.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped184.2 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL209.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active210.5 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - PAPER219.8 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL244.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H256.5 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - PAPER261.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active261.2 ft. MWM - Water Mark, 5 %of cross sectional area261.2 ft. MWL - Water Level, 5 %of cross sectional area262.9 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SL275 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (3)

  • General Observation - 12" VCP

    8 ft. - General Observation - 12" VCP

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start - PAPER

    210.5 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - PAPER

  • Water Mark, 5 %of cross sectional area

    261.2 ft. - Water Mark, 5 %of cross sectional area

Observations (26)

DistanceCodeObservation
65.1FCH
120.7FCSL
256.5DSZPAPER
210.5DSZPAPER
110.5TFCCapped
42.2FCSL
209.2TFActive
261.2TFActive
261.2MWM
261.2MWL
0MWM
0AMH5:15AM
0MWLNO FLOW
275AMH5:50AM
136.7FCSL
59.5TFActive
161.8TFCCapped
262.9FCSL
8MGO12" VCP
244.2FCH
81.4FCSL
219.8FCSL
184.2FCSL
136.7MWLNO FLOW
18FLSLIGHT
0MGOConn. @ Mh, 3 O' Clock. Capped

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-05-30T05:03:01-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false