Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2019, 06:44 PM
  • Section#3_29 0517_29 0516A__672019__I 0155.mp4

Date
06/07/2019
W/O
0771885
Weather
Dry
Operator/Surveyor
BRAR
Sewer ID
Z01106
PipeID
P24567
Time
11:44 AM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I 0155
Sewer Name
29 19TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20190607SB_19TH_STREET_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0517
Downstream MH
29 0516A
Dir. of Survey
Downstream
Length Surveyed
65 ft.
Total Length
65 ft.
Structural Index
3
Structural Quick
513A
Structural Rating
65
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
65
Pipe schematic from manhole 29 0517 to 29 0516A
MH: 29 0517MH: 29 0516Adownstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 11:47 AM0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area4.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.2 ft. MGP - General Photograph - SPALLING25.3 ft. MGP - General Photograph26.9 ft. B - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES27.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"30 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"34.3 ft. MGP - General Photograph37.2 ft. MGP - General Photograph64 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish64 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish65 ft. AMH - Downstream Manhole, Survey Ends - 12:23 PM @ LAMP POST65 ft. MGP - General Photograph - LAMP HOLE, POSSIBLE BROKEN CAP

Observation photos (8)

  • General Photograph - SPALLING

    12.2 ft. - General Photograph - SPALLING

  • General Photograph

    25.3 ft. - General Photograph

  • Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

    26.9 ft. - Broken, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    27.8 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    30 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

  • General Photograph

    34.3 ft. - General Photograph

  • General Photograph

    37.2 ft. - General Photograph

  • General Photograph - LAMP HOLE, POSSIBLE BROKEN CAP

    65 ft. - General Photograph - LAMP HOLE, POSSIBLE BROKEN CAP

Observations (17)

DistanceCodeObservation
26.9B
65AMH12:23 PM @ LAMP POST
64CM
65MGPLAMP HOLE, POSSIBLE BROKEN CAP
0MGOROACHES @ MH
34.3MGP
30TFA
4.9SSS
25.3MGP
27.8TFA
64SSS
0AMH11:47 AM
37.2MGP
0MWM
12.2MGPSPALLING
4.9CM
0MWL

Properties (6)

additional_info
U-0618-0703002249
custom_field_two
3
customer
LACSD
datetime
2019-06-07T11:44:04-07:00
documentation
BRAR, FRANKLIN, IGNACIO
is_lateral_inspection
false