Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2018, 10:10 AM
  • J 0107_J 0462 _22062018_031836.mp4

Date
06/22/2018
W/O
707285
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00064
PipeID
P22724
Time
3:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5745
Sewer Name
J JOINT OUTFALL J - UNIT 2E
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
25
Purpose
Routine Assessment
Project
WO_707285_TV05291_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
J 0462
Downstream MH
J 0107
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole J 0462 to J 0107
MH: J 0462MH: J 0107upstream0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. AMH - Upstream Manhole, Survey Ends - J 01072 ft. AMH - Downstream Manhole, Survey Begins - J 04622 ft. MWL - Water Level, 50 %of cross sectional area2 ft. MWM - Water Mark, 60 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Upstream Manhole, Survey Ends - J 0107

    2 ft. - Upstream Manhole, Survey Ends - J 0107

Observations (6)

DistanceCodeObservation
0AMHJ 0462
0MWL
2SAP
2SSS
2AMHJ 0107
0MWM

Properties (6)

additional_info
SC359711
custom_field_two
4
customer
LACSD
datetime
2018-06-22T03:10:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false