Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2018, 09:21 AM
  • 15 0672_15 0671 _13062018_023027.mp4

Date
06/13/2018
W/O
707118
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00602
PipeID
P12564
Time
2:21 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5194
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_707118_TV15005_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0672
Downstream MH
15 0671
Dir. of Survey
Downstream
Length Surveyed
32.1 ft.
Total Length
32.1 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0672 to 15 0671
MH: 15 0672MH: 15 0671downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 15 06720 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"29 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish29 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish29 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish32.1 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH32.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0671

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

    2.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
32.1MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
4SSS
2.1CL
2DAGS
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
32.1AMH15 0671
29SAV
29DAGS
0AMH15 0672
2SAV
0MWM
29SSS
0MWL
9TFC

Properties (6)

additional_info
SC359517
custom_field_two
2
customer
LACSD
datetime
2018-06-13T02:21:28-07:00
documentation
PROPIPE
is_lateral_inspection
false