Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2018, 07:15 AM
  • 15 0664_15 0663 _12062018_003702.mp4

Date
06/12/2018
W/O
707118
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00602
PipeID
P12556
Time
12:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5191
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_707118_TV15005_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0664
Downstream MH
15 0663
Dir. of Survey
Downstream
Length Surveyed
298 ft.
Total Length
298 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 15 0664 to 15 0663
MH: 15 0664MH: 15 0663downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 15 06640 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MWM - Water Mark, 50 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start32.6 ft. LFD - Lining Failure Detached, from 09 to 03 o'clock, within 8 inches of joint: YES33.3 ft. SMW - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES34.3 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES43.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish296.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish296.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish298 ft. AMH - Downstream Manhole, Survey Ends - 15 0663

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Lining Failure Detached, from 09 to 03 o'clock, within 8 inches of joint: YES

    32.6 ft. - Lining Failure Detached, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES

    33.3 ft. - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    34.3 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
32.6LFD
155.6TFC
125.5TB
2.2SSS
33.3SMW
296.4SSS
206.9TFC
264.5TF
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
261.3TFC
0AMH15 0664
2MWM
296.4DAGS
296.4SAP
43.3TFC
0MWL
2.1DAGS
2.1SAP
34.3B
298AMH15 0663
217.6TB

Properties (6)

additional_info
SC359514
custom_field_two
1
customer
LACSD
datetime
2018-06-12T00:15:04-07:00
documentation
PROPIPE
is_lateral_inspection
false