Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2018, 08:49 AM
  • 19 0296_19 0295_18062018_015301.mp4

Date
06/18/2018
W/O
707048
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00718
PipeID
P20183
Time
1:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5732
Sewer Name
19 ARTESIA-CERRITOS TRUNK
City
ARTESIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_707048_TV19059_JUN2018
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0295
Downstream MH
19 0296
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 19 0295 to 19 0296
MH: 19 0295MH: 19 0296upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF THE UPLEG OF D/S NORTHWEST SIPHON.2 ft. AMH - Downstream Manhole, Survey Begins - 19 0295, NORTHWEST SIPHON.2 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF THE UPLEG OF D/S NORTHWEST SIPHON.

    2 ft. - Survey Abandoned - VIEW OF THE UPLEG OF D/S NORTHWEST SIPHON.

Observations (5)

DistanceCodeObservation
0AMH19 0295, NORTHWEST SIPHON.
0MWM
2DAGS
0MWL
2MSAVIEW OF THE UPLEG OF D/S NORTHWEST SIPHON.

Properties (6)

additional_info
SC359398
custom_field_two
3
customer
LACSD
datetime
2018-06-18T01:49:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false