Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2018, 07:53 AM
  • 18 0017_18 0016 _11062018_012354.mp4

Date
06/11/2018
W/O
706968
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00713
PipeID
P13833
Time
12:53 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5190
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
15
Purpose
Routine Assessment
Project
WO_706968_TV18059_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0017
Downstream MH
18 0016
Dir. of Survey
Downstream
Length Surveyed
145.5 ft.
Total Length
145.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0017 to 18 0016
MH: 18 0017MH: 18 0016downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00170 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG RESIDUE18.1 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"38.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES143.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish143.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish143.2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish145.5 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH145.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0016

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MAG RESIDUE

    2.4 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG RESIDUE

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    38.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
0AMH18 0017
143.2SAV
2.4DAGS
145.5MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
143.2DAGS
0MWL
38.2CM
0MWM
18.1TB
145.5AMH18 0016
2.4SAV
143.2DAZ
0MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
2.4DAZMAG RESIDUE

Properties (6)

additional_info
SC359513
custom_field_two
3
customer
LACSD
datetime
2018-06-11T00:53:42-07:00
documentation
PROPIPE
is_lateral_inspection
false