Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2018, 07:52 AM
  • 15 0097A_15 0097_20062018_010648.mp4

Date
06/20/2018
W/O
706913
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00590
PipeID
P11975
Time
12:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5737
Sewer Name
15 ABBEY STREET TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
WO_706913_TV15007_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0097A
Downstream MH
15 0097
Dir. of Survey
Downstream
Length Surveyed
270.2 ft.
Total Length
270.2 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
116
Pipe schematic from manhole 15 0097A to 15 0097
MH: 15 0097AMH: 15 0097downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0097A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"18.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"67.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"74.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES89.8 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES118.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"166.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"169.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"189.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES218.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"221 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"240.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES263.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"266.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"267.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish270.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0097270.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE270.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    74.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    89.8 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    189.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    240.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
270.2AMH15 0097
67.1TFC
267.7DAGS
189.4CS
118.4TF
0AMH15 0097A
166.4TFC
270.2MGOCOCKROACHES IN MANHOLE
240.8CL
15.8TFC
221TFC
0MWM
121.1TFC
0MGOCOCKROACHES IN MANHOLE
89.8CM
2DAGS
266.3TFC
270.2MGOCONNECTION AT MH 9 O'CLOCK
218.3TFC
263.3TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
169.3TF
74.5CM
18.3TFC
0MWL
69.5TFC

Properties (6)

additional_info
SC359703
custom_field_two
3
customer
LACSD
datetime
2018-06-20T00:52:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false