Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 12, 2018, 06:21 AM
  • 20 0435_20 0434 _11062018_233504.mp4

Date
06/11/2018
W/O
706912
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00749
PipeID
P19383
Time
11:21 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5725
Sewer Name
20 10TH STREET EAST CONNECTION TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
12
Purpose
Routine Assessment
Project
WO_706912_TV20001_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
20 0435
Downstream MH
20 0434
Dir. of Survey
Downstream
Length Surveyed
322.7 ft.
Total Length
322.7 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 20 0435 to 20 0434
MH: 20 0435MH: 20 0434downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 20 04350 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start54.3 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES82.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES120.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"122.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"179.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"229.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"235.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"265 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"289.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"310.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"322.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish322.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE322.7 ft. AMH - Downstream Manhole, Survey Ends - 20 0434

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    54.3 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    82.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
310.5TF
2DAGS
82.3CM
54.3FM
0MWL
0AMH20 0435
235.2TFA
322.7MGOCOCKROACHES IN MANHOLE
179.5TFC
289.5TFA
0MGOCOCKROACHES IN MANHOLE
265TFC
229.5TFA
122.5TFC
322.7AMH20 0434
120.7TFA
0MWM
322.6DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC359391
custom_field_two
3
customer
LACSD
datetime
2018-06-11T23:21:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false