Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2018, 09:26 AM
  • C 0343_C 0342_7122018_030349.mp4

Date
07/12/2018
W/O
0716531
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00138
PipeID
P09806
Time
2:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0932
Sewer Name
C JOINT OUTFALL C - UNIT 7B
City
HAWAIIAN GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180712MDM_JOINT_OUTFALL_C_UNIT_7B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
C 0342
Downstream MH
C 0343
Dir. of Survey
Upstream
Length Surveyed
162.8 ft.
Total Length
162.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole C 0342 to C 0343
MH: C 0342MH: C 0343upstream0 ft. AMH - Upstream Manhole, Survey Ends(COMPLETED REVERSE INSPECTION) - 3:15AM (COMPLETED REVERSE INSPECTION0.4 ft. MGO - General Observation - MAG COAT 98% FINISH0.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE33.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE96.2 ft. SAV - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG160.8 ft. MGO - General Observation - MAG COAT 98% START 8:00 TO 4:00160.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT162.8 ft. MWM - Water Mark, 30 %of cross sectional area162.8 ft. MWL - Water Level, 0 %of cross sectional area - NO FLOW162.8 ft. AMH - Downstream Manhole, Survey Begins - 3:05AM

Observation photos (4)

  • General Observation - MAG COAT 98% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 98% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

    66.6 ft. - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    129.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (10)

DistanceCodeObservation
2MGOMAG COAT 98% START 8:00 TO 4:00
0MWM
162.4MGOMAG COAT 98% FINISH
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
129.3SSSBLISTERING PEELING CONCRETE
162.8AMH3:15AM (COMPLETED REVERSE INSPECTION
162.4SSSBLISTERING PEELING CONCRETE
0MWLNO FLOW
0AMH3:05AM
66.6SAVSEVERE AGG

Properties (6)

custom_field_three
VISIBLE SEVERE AGG- 98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-07-12T02:26:10-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false