Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2018, 08:52 AM
  • F 0212A_F 0212_7102018_030130.mp4

Date
07/10/2018
W/O
0712061
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00048
PipeID
P10343
Time
1:52 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0927
Sewer Name
F JOINT OUTFALL F - UNIT 7F
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Routine Assessment
Project
20180710MDM_JOINT_OUTFALL_F_UNIT_7F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
31.6299991607666 in.
Upstream MH
F 0212A
Downstream MH
F 0212
Dir. of Survey
Downstream
Length Surveyed
167.6 ft.
Total Length
167.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole F 0212A to F 0212
MH: F 0212AMH: F 0212downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2.1 ft. MGO - General Observation - 31.63" RCP-CIPP11.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active64.1 ft. MGO - General Observation - 31.63" RCP-CIPP96.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open167.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active167.1 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: NO - INSIDE MH167.6 ft. AMH - Downstream Manhole, Survey Ends - 3:15AM

Observation photos (3)

  • General Observation - 31.63" RCP-CIPP

    2.1 ft. - General Observation - 31.63" RCP-CIPP

  • General Observation - 31.63" RCP-CIPP

    64.1 ft. - General Observation - 31.63" RCP-CIPP

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: NO - INSIDE MH

    167.1 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: NO - INSIDE MH

Observations (11)

DistanceCodeObservation
64.1MGO31.63" RCP-CIPP
0AMH2:55AM
96.8TBOpen
167.1MGOConn. @ Mh, 3 O' Clock. Active
11.7TBActive
0MWL
2.1MGO31.63" RCP-CIPP
0.1MGOConn. @ Mh, 9 O' Clock. Active
167.1DAGSINSIDE MH
0MWM
167.6AMH3:15AM

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2018-07-10T01:52:31-07:00
documentation
MARTIN,OLIVER 111,YOUNG
is_lateral_inspection
false
lining
CIPP