Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2018, 07:32 AM
  • F 0215_F 0214_7102018_004314.mp4

Date
07/10/2018
W/O
0712061
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00048
PipeID
P10345
Time
12:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0927
Sewer Name
F JOINT OUTFALL F - UNIT 7F
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Routine Assessment
Project
20180710MDM_JOINT_OUTFALL_F_UNIT_7F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
31.6299991607666 in.
Upstream MH
F 0214
Downstream MH
F 0215
Dir. of Survey
Upstream
Length Surveyed
33.1 ft.
Total Length
33.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole F 0214 to F 0215
MH: F 0214MH: F 0215upstream0 ft. AMH - Upstream Manhole, Survey Ends - 12:50AM2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: NO11.9 ft. MGO - General Observation - CIPP LINER25.1 ft. MGO - General Observation - 33" RCP +CIPP33.1 ft. AMH - Downstream Manhole, Survey Begins - 12:40AM33.1 ft. MWL - Water Level, 10 %of cross sectional area33.1 ft. MWM - Water Mark, 20 %of cross sectional area33.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observation photos (2)

  • General Observation - 33" RCP +CIPP

    8 ft. - General Observation - 33" RCP +CIPP

  • General Observation - CIPP LINER

    21.2 ft. - General Observation - CIPP LINER

Observations (8)

DistanceCodeObservation
0AMH12:40AM
0MWL
0MWM
8MGO33" RCP +CIPP
33.1AMH12:50AM
0MGOConn. @ Mh, 9 O' Clock. Active
31DAGS
21.2MGOCIPP LINER

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2018-07-10T00:32:35-07:00
documentation
MARTIN,OLIVER 111,YOUNG
is_lateral_inspection
false
lining
CIPP