Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2018, 08:24 AM
  • Section#1_29 0481_29 0480__792018__ I0030.mp4

Date
07/09/2018
W/O
0711163
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00789
PipeID
P24527
Time
1:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0030
Sewer Name
29 CHERRY AVENUE TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180709MDM_CHERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0481
Downstream MH
29 0480
Dir. of Survey
Downstream
Length Surveyed
365.1 ft.
Total Length
365.1 ft.
Structural Index
2
Structural Quick
5142
Structural Rating
149
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 29 0481 to 29 0480
MH: 29 0481MH: 29 0480downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM3.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL5.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE7.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL7.5 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SL11.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6" - STUB13.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT20.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL30.4 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H47.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H57.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL60.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL61.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB63.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H63.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL90.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL100.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H104.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL104.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL107.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES107.5 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL108.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB143.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H150.7 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H150.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL154.3 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL157.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL157.5 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SL158.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB166.8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL166.8 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H197.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H200.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL203.9 ft. FC - Fracture Circumferential, from 05 to 07 o'clock, within 8 inches of joint: YES - SL203.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H203.9 ft. FC - Fracture Circumferential, from 04 to 06 o'clock, within 8 inches of joint: YES - SL204.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL207.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL208.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN210.1 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL210.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL213.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL219.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H219.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H223.2 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H230.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H233.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL240.3 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H243.6 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL243.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL247 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL257.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL261.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN269.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL276.6 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H276.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL287.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL290.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL291.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL300.4 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - SL301.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB302.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL302.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL321.7 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H321.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H325.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL330.8 ft. MLC - Lining Change, Other (enter details in Field 39) - LINER START343.1 ft. MLC - Lining Change, Other (enter details in Field 39) - LINER FINISH343.7 ft. FM - Fracture Multiple, from 07 to 06 o'clock, within 8 inches of joint: YES - MODERATE343.7 ft. B - Broken, from 03 to 05 o'clock, within 8 inches of joint: YES - MODEERATE FRACTURE359 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL365.1 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (5)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    287.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - SL

    300.4 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - SL

  • Lining Change, Other (enter details in Field 39) - LINER START

    330.8 ft. - Lining Change, Other (enter details in Field 39) - LINER START

  • Fracture Multiple, from 07 to 06 o'clock, within 8 inches of joint: YES - MODERATE

    343.7 ft. - Fracture Multiple, from 07 to 06 o'clock, within 8 inches of joint: YES - MODERATE

  • Broken, from 03 to 05 o'clock, within 8 inches of joint: YES - MODEERATE FRACTURE

    343.7 ft. - Broken, from 03 to 05 o'clock, within 8 inches of joint: YES - MODEERATE FRACTURE

Observations (74)

DistanceCodeObservation
230.2FLH
166.8FCSL
0MWM
208.3TFOPEN
166.8FCH
243.6FCSL
90.6FLSL
108.5TFCSTUB
219.7FCH
302.9FLSL
61.7TFCSTUB
30.4FLH
219.7FCH
63.5FLH
7.5FCSL
60.9FCSL
291.7FLSL
276.6FCH
290.2FLSL
3.1FCSL
200.5FCSL
302.9FCSL
325.3FCSL
213.4FCSL
321.7FLH
47.2FLH
63.5FCSL
365.1AMH2:35AM
107.5FC
207.4FCSL
13.5FCSLIGHT
269.7FCSL
343.1MLCLINER FINISH
287.3FLSL
100.8FCH
197.2FLH
261.6TFOPEN
300.4FMSL
243.6FCSL
210.1FCSL
7.5FCSL
301.1TFCSTUB
150.7FCH
321.7FLH
210.1FLSL
276.6FCSL
0MWL
154.3FCSL
20.3FCSL
343.7FMMODERATE
158.5TFCSTUB
204.2FLSL
11.8TFCSTUB
150.7FLSL
257.3FCSL
157.5FCSL
104.1FCSL
107.5FCSL
330.8MLCLINER START
203.9FCSL
343.7BMODEERATE FRACTURE
57.4FLSL
0AMH1:25AM
143.7FCH
104.1FCSL
233.5FLSL
247FLSL
223.2FLH
240.3FCH
157.5FCSL
203.9FCH
359FCSL
203.9FCSL
5.5FLHAIRLINE

Properties (6)

custom_field_three
BROKEN PIPE MODERATE FRACTURE
custom_field_two
2
customer
LACSD
datetime
2018-07-09T01:24:26-07:00
documentation
MARTIN,OLIVER 111,YOUNG
is_lateral_inspection
false