Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 24, 2018, 09:55 AM
  • 05 1693_05 1692_10242018_051629.mp4

Date
10/24/2018
W/O
0734333
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06919
Time
2:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1025
Sewer Name
05 LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Capital Improvement Program Assesment
Project
20181019MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1693
Downstream MH
05 1692
Dir. of Survey
Downstream
Length Surveyed
296.5 ft.
Total Length
296.5 ft.
Structural Index
3
Structural Quick
3B23
Structural Rating
45
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
45
Pipe schematic from manhole 05 1693 to 05 1692
MH: 05 1693MH: 05 1692downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM3.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT3.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT4.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS10.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL10.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - SL41.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL51.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL57.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO - SL65.9 ft. B - Broken, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACRURE70.3 ft. B - Broken, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE73.1 ft. MGO - General Observation - 21" VCP84 ft. B - Broken, at 09 o'clock, within 8 inches of joint: YES, Finish - SLIGHT84 ft. B - Broken, at 03 o'clock, within 8 inches of joint: YES, Finish - SLIGHT97.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - SL97.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL141.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL141.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL165.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL165.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - SL226.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL229.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL296 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 155 SLIGHT AT JOINTS296 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - SL296 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS296 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS296 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 40% HAIRLINE AT JOINTS296 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - SL296.5 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (12)

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS

    8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS

    8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

    41.5 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

    51.8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO - SL

    57.7 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: NO - SL

  • Broken, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACRURE

    65.9 ft. - Broken, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACRURE

  • Broken, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE

    70.3 ft. - Broken, at 09 o'clock, within 8 inches of joint: YES, Start - SLIGHT FRACTURE

  • General Observation - 21" VCP

    73.1 ft. - General Observation - 21" VCP

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

    141.6 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

    141.6 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

    226.8 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

    229.8 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SL

Observations (35)

DistanceCodeObservation
165.9FLSL
296FL155 SLIGHT AT JOINTS
226.8FLSL
8FCHAIRLINE AT JOINTS
296FLSL
57.7FLSL
165.9FLSL
84BSLIGHT
70.3BSLIGHT FRACTURE
10.2FLSL
0MWM
141.6FLSL
4.5FCSL
84BSLIGHT
8FLSLIGHT AT JOINTS
10.2FLSL
296FL15% HAIRLINE AT JOINTS
97.7FLSL
65.9BSLIGHT FRACRURE
8FCSLIGHT AT JOINTS
296FC40% SLIGHT AT JOINTS
296FC40% HAIRLINE AT JOINTS
51.8FLSL
73.1MGO21" VCP
97.7FLSL
296.5AMH5:45AM
296FLSL
41.5FLSL
3.1FLSLIGHT
229.8FLSL
0MWL
8FLHAIRLINE AT JOINTS
3.1FLSLIGHT
141.6FLSL
0AMH5:15AM

Properties (6)

custom_field_three
BROKEN PIPE -SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
1
customer
LACSD
datetime
2018-10-24T02:55:09-07:00
documentation
MARTIN,OLIVER 111,BRAR
is_lateral_inspection
false