Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 18, 2018, 04:06 PM
  • J 0332_J 0331_10182018_102436.mp4

Date
10/18/2018
W/O
0689827
Weather
Dry
Operator/Surveyor
SANTIAGO ORBEGON
Sewer ID
Z00059
PipeID
P11576
Time
9:06 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7832
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES
Loc. details
Woods
Location Code
E
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
10
Purpose
Routine Assessment
Project
20181018SHO_JOINT_OUTFALL_J_UNIT_1G
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
J 0332
Downstream MH
J 0331
Dir. of Survey
Downstream
Length Surveyed
175 ft.
Total Length
175 ft.
Structural Index
4
Structural Quick
5249
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
50
Pipe schematic from manhole J 0332 to J 0331
MH: J 0332MH: J 0331downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 03320 ft. MWL - Water Level, 15 %of cross sectional area34.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES68 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES80.5 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES80.5 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES101.5 ft. FM - Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES105 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES109.1 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES133.1 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES133.1 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES145.8 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES157.7 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES165.8 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES, Start169.7 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish170.1 ft. B - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES, Start173.5 ft. B - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish175 ft. AMH - Downstream Manhole, Survey Ends - J 0331

Observation photos (12)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    34.8 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    68 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

    80.5 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    80.5 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

    101.5 ft. - Fracture Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    105 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    109.1 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    133.1 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    145.8 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    157.7 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES, Start

    165.8 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 08 to 09 o'clock, within 8 inches of joint: YES, Start

    170.1 ft. - Broken, from 08 to 09 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
0MWM
175AMHJ 0331
109.1FM
80.5SSS
0AMHJ 0332
133.1FM
169.7B
101.5FM
157.7FM
68FM
133.1FM
170.1B
173.5B
145.8FM
165.8B
0MWL
34.8CL
80.5B
105FM

Properties (6)

custom_field_three
BROKEN PIPE & FRACTURES
custom_field_two
2
customer
LACSD
datetime
2018-10-18T09:06:10-07:00
documentation
OBREGON, YOUNG, CASTILLO, RUVALCABA
is_lateral_inspection
false