Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2017, 11:05 AM
  • 02 0720_02 0719A_05122017_030607.mp4

Date
12/05/2017
W/O
674429
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00294
PipeID
P03274
Time
3:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5260
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
WO_674429_TV02351_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0720
Downstream MH
02 0719A
Dir. of Survey
Downstream
Length Surveyed
319.7 ft.
Total Length
319.7 ft.
Structural Index
4
Structural Quick
4K32
Structural Rating
242
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
242
Pipe schematic from manhole 02 0720 to 02 0719A
MH: 02 0720MH: 02 0719Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 07200 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK6.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start10.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start18.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish29.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start29.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish95.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish319.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0719A

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    18.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    29.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MWM
319.7FM
29.8FL
6.9TFC
319.7AMH02 0719A
99.1TFC
18.1FL
222.4TF
10.7TFC
0AMH02 0720
95.1TF
18.1CL
29.7FM
0MWL
8.1CL
0MGOCONNECTION AT MH 9 O'CLOCK
219.3TF

Properties (6)

additional_info
SC346289
custom_field_two
3
customer
LACSD
datetime
2017-12-05T03:05:41-08:00
documentation
PROPIPE
is_lateral_inspection
false