Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2017, 06:10 AM
  • A 0581_A 1090 _04122017_224741.mp4

Date
12/04/2017
W/O
674024
Weather
Dry
Operator/Surveyor
ERUIZ
Sewer ID
Z00316
PipeID
P07786
Time
10:10 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5151
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_674024_TV21041_DEC2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
72 in.
Width
72 in.
Upstream MH
A 0581
Downstream MH
A 1090
Dir. of Survey
Downstream
Length Surveyed
902.8 ft.
Total Length
902.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole A 0581 to A 1090
MH: A 0581MH: A 1090downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 05810 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area10 ft. MGO - General Observation - MAGNESIUM COATING START, 70%10 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start893.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish893.7 ft. MGO - General Observation - MAGNESIUM COATING END, 70%902.8 ft. AMH - Downstream Manhole, Survey Ends - A 1090

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMHA 0581
893.7MGOMAGNESIUM COATING END, 70%
893.6SAP
902.8AMHA 1090
10MGOMAGNESIUM COATING START, 70%
10SAP
0MWM
0MWL

Properties (6)

additional_info
SC346461
custom_field_two
3
customer
LACSD
datetime
2017-12-04T22:10:05-08:00
documentation
PROPIPE
is_lateral_inspection
false