Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2017, 07:47 AM
  • 02 1282_02 1281B_30112017_234744.mp4

Date
11/30/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03799
Time
11:47 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5256
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 1282
Downstream MH
02 1281B
Dir. of Survey
Downstream
Length Surveyed
245.4 ft.
Total Length
245.5 ft.
Structural Index
4
Structural Quick
4D3D
Structural Rating
168
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
168
Pipe schematic from manhole 02 1282 to 02 1281B
MH: 02 1282MH: 02 1281Bdownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12820 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area3.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start116.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish127.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start212.3 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK AT THE JOINT245.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish245.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1281B

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    127.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK AT THE JOINT

    212.3 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES - POSSIBLE BREAK AT THE JOINT

Observations (10)

DistanceCodeObservation
245.5CM
0MWL
0AMH02 1282
116.2FM
3.1FM
245.5AMH02 1281B
127.4CM
212.3FMPOSSIBLE BREAK AT THE JOINT
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM

Properties (6)

additional_info
SC346285
custom_field_two
2
customer
LACSD
datetime
2017-11-30T23:47:30-08:00
documentation
PROPIPE
is_lateral_inspection
false