Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 06:16 AM
  • 02 1302_02 1301B_28112017_221748.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03821
Time
10:16 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5053
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1302
Downstream MH
02 1301B
Dir. of Survey
Downstream
Length Surveyed
142.4 ft.
Total Length
142.4 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole 02 1302 to 02 1301B
MH: 02 1302MH: 02 1301Bdownstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 13020 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area5.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1301B142.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
142.4AMH02 1301B
0MGOCONNECTION AT MH 3 O'CLOCK
89.4TB
90.3TFC
0AMH02 1302
126.3TF
5.4CM
0MWM
140.1TFC
142.4CM
138.5TB
0MWL
54.5TF
95.8TF
12.1TF

Properties (6)

additional_info
SC346282
custom_field_two
3
customer
LACSD
datetime
2017-11-28T22:16:21-08:00
documentation
PROPIPE
is_lateral_inspection
false