Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2017, 08:26 AM
  • 02 1279_02 1278_01122017_003017.mp4

Date
12/01/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03794
Time
12:26 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5256
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 1279
Downstream MH
02 1278
Dir. of Survey
Downstream
Length Surveyed
320 ft.
Total Length
320.1 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
182
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
182
Pipe schematic from manhole 02 1279 to 02 1278
MH: 02 1279MH: 02 1278downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12790 ft. MWL - Water Level, 10 %of cross sectional area18.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start84.5 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES320.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish320.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1278

Observation photos (2)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    18.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    84.5 ft. - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWM
0AMH02 1279
18.5CM
320.1CM
320.1AMH02 1278
0MWL
84.5FC

Properties (6)

additional_info
SC346285
custom_field_two
3
customer
LACSD
datetime
2017-12-01T00:26:03-08:00
documentation
PROPIPE
is_lateral_inspection
false