Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2018, 09:39 AM
  • Section#2_A 0514_A 0513__1122018__G6915.mp4

Date
01/12/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00315
PipeID
P07750
Time
1:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6915
Sewer Name
A JOA-1A DISTRICT 5 INTERCEPTOR
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20180112MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
A 0514
Downstream MH
A 0513
Dir. of Survey
Downstream
Length Surveyed
816.8 ft.
Total Length
816.8 ft.
Structural Index
5
Structural Quick
5`4`
Structural Rating
1487
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
1487
Pipe schematic from manhole A 0514 to A 0513
MH: A 0514MH: A 0513downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MG COAT 99% START 8:00 TO 4:002 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT43.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR244.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR364 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR738.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT816.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR UNDER MAG COAT816.1 ft. MGO - General Observation - MAG COAT 100% FINISH816.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT816.8 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (7)

  • General Observation - MG COAT 99% START 8:00 TO 4:00

    2 ft. - General Observation - MG COAT 99% START 8:00 TO 4:00

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    43.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    244.1 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    364 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    738.7 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

Observations (14)

DistanceCodeObservation
816.1SRCCIRCUM REBAR UNDER MAG COAT
738.7SRCCIRCUM REBAR UNDER MAG COAT
816.8AMH3:10AM
0MWM
364SRCCIRCUM REBAR
2MGOMG COAT 99% START 8:00 TO 4:00
43.1SRCCIRCUM REBAR
2SAMSEVERE AGG UNDER MAG COAT
0AMH2:10AM
816.1MGOMAG COAT 100% FINISH
0MWL
816.1SAMSEVERE AGG UNDER MAG COAT
2SRCCIRCUM REBAR UNDER MAG COAT
244.1SRCCIRCUM REBAR

Properties (6)

custom_field_three
CORRODED REBAR UNDER MAG COAT
custom_field_two
1
customer
LACSD
datetime
2018-01-12T01:39:54-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false