Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2018, 06:12 AM
  • 22 0502_22 0501 _19042018_233321.mp4

Date
04/19/2018
W/O
695664
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00800
PipeID
P16841
Time
11:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5573
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_695664_TV22031_APR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
22 0502
Downstream MH
22 0501
Dir. of Survey
Downstream
Length Surveyed
332.2 ft.
Total Length
332.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0502 to 22 0501
MH: 22 0502MH: 22 0501downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 05020 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 02 to 10 o'clock, within 8 inches of joint: YES, Start13.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"16.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"61.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"64.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"64.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"83.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"113 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"115.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"164.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"167.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"209.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"212.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"235.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES260.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"263.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"314.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"318.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"329.9 ft. SAP - Surface Aggregate Projecting, from 02 to 10 o'clock, within 8 inches of joint: YES, Finish332.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK332.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0501

Observation photos (2)

  • Surface Aggregate Projecting, from 02 to 10 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 02 to 10 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    235.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
263.8TFC
113TFC
332.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH22 0502
115.9TFC
314.9TFC
61.3TFC
318.1TFC
164.1TFC
260.8TFC
332.2AMH22 0501
167.3TFC
64.7TBA
209.5TFC
64.7TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
13.2TFC
83.2TBA
212.5TFC
0MWL
329.9SAP
2SAP
235.3CM
16.6TFC
0MWM

Properties (6)

additional_info
SC358532
custom_field_two
2
customer
LACSD
datetime
2018-04-19T23:12:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false