Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2018, 10:40 AM
  • 29 0198_29 0177 _29012018_025222.mp4

Date
01/29/2018
W/O
684976
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01025
PipeID
P24097
Time
2:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5425
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_684976_TV29048_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0198
Downstream MH
29 0177
Dir. of Survey
Downstream
Length Surveyed
315.4 ft.
Total Length
315.4 ft.
Structural Index
5
Structural Quick
5200
Structural Rating
10
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
4
Overall Quick
Overall Rating
20
Pipe schematic from manhole 29 0198 to 29 0177
MH: 29 0198MH: 29 0177downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: NO0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 01982 ft. MGO - General Observation - SPALLING FROM 8 TO 4 O'CLOCK @ 2' MARK TO 314'45.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.3 ft. RML - Roots Medium Lateral, at 10 o'clock, 20 %, within 8 inches of joint: NO96.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.1 ft. RML - Roots Medium Lateral, at 10 o'clock, 15 %, within 8 inches of joint: NO147.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"246.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: NO295.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.4 ft. MSA - Survey Abandoned - BEND IN PIPE315.4 ft. LD - Alignment Down, 90 %

Observation photos (1)

  • Alignment Down, 90 %

    315.4 ft. - Alignment Down, 90 %

Observations (22)

DistanceCodeObservation
93.8TFC
315.4MSABEND IN PIPE
295.6TFC
298.2TFC
144.5TFC
248.8TFC
96.3RML
0MWL
195.4TFC
246.4TFC
48.1TF
45.5TFC
0B
0MWM
315.4LD
96.3TF
198.1TFC
147.1RML
258B
2MGOSPALLING FROM 8 TO 4 O'CLOCK @ 2' MARK TO 314'
0AMH29 0198
147.1TF

Properties (6)

additional_info
SC347060
custom_field_two
1
customer
LACSD
datetime
2018-01-29T02:40:42-08:00
documentation
PROPIPE
is_lateral_inspection
false