Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2017, 06:22 AM
  • G 0060G 0059District 01_011217.mp4

Date
01/12/2017
W/O
613592
Weather
Damp
Operator/Surveyor
R.VARGAS
Sewer ID
Z00345
PipeID
P10423
Time
10:22 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4077
Sewer Name
G JOINT OUTFALL G - UNIT 5
City
COMPTON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
WO_613592_TV01215_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
G 0060
Downstream MH
G 0059
Dir. of Survey
Downstream
Length Surveyed
337.6 ft.
Total Length
337.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L12
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole G 0060 to G 0059
MH: G 0060MH: G 0059downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 00600 ft. MGO - General Observation - LINER0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.9 ft. MGO - General Observation - MAGNESIUM H.O. START2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start77.5 ft. LFW - Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: YES333.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.9 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH337.6 ft. VC - Vermin Cockroach337.6 ft. AMH - Downstream Manhole, Survey Ends - G 0059337.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK MADE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: YES

    77.5 ft. - Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
77.5LFW
0AMHG 0060
337.6VC
2.9MGOMAGNESIUM H.O. START
333.9DAGS
333.9MGOMAGNEZIUM H.O. FINISH
0MGOLINER
0VC
0MWM
2.9DAGS
0MWL
337.6AMHG 0059
337.6MGOCONNECTION AT MH 3 O'CLOCK MADE

Properties (7)

additional_info
SC318618
custom_field_two
4
customer
LACSD
datetime
2017-01-12T22:22:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP