Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 30, 2016, 09:17 AM
  • 01 0692_01 0691_30092016_021846.mp4

Date
09/30/2016
W/O
591536
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01401
Time
2:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3596
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_591536_TV01117_SEP2016
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0692
Downstream MH
01 0691
Dir. of Survey
Downstream
Length Surveyed
406.6 ft.
Total Length
406.7 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
237
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
237
Pipe schematic from manhole 01 0692 to 01 0691
MH: 01 0692MH: 01 0691downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06920 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 70%6.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start402.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish406.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0691

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    6.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (7)

DistanceCodeObservation
2MGOMAG COAT 70%
0AMH01 0692
6.9SAP
402.4SAP
406.7AMH01 0691
0MWL
0MWM

Properties (6)

additional_info
SC306191
custom_field_two
3
customer
LACSD
datetime
2016-09-30T02:17:36-07:00
documentation
PROPIPE
is_lateral_inspection
false