- Date
- 10/03/2016
- W/O
- 591536
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00199
- PipeID
- P01389
- Time
- 10:26 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K3598
- Sewer Name
- 01 CALIFORNIA AVENUE EXTENSION TRUNK
- City
- SOUTH GATE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- WO_591536_TV01117_SEP2016
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Width
- 33 in.
- Upstream MH
- 01 0680
- Downstream MH
- 01 0679
- Dir. of Survey
- Downstream
- Length Surveyed
- 476.5 ft.
- Total Length
- 476.5 ft.
- Structural Index
- 4
- Structural Quick
- 5532
- Structural Rating
- 31
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 31
Pipe schematic from manhole 01 0680 to 01 0679 Observation photos (6)

3.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

194.3 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

216.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

290.7 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

345.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

353.2 ft. - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: YES