- Date
- 05/08/2018
- W/O
- PENDING
- Weather
- Dry
- Operator/Surveyor
- FRANKLIN
- Sewer ID
- Z00429
- PipeID
- P20008
- Time
- 1:04 PM
- Certificate
- U-415-06024039
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Heavy Cleaning
- Media Label
- G7705
- Sewer Name
- 05 COLDEN AVENUE TRUNK
- City
- LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- 20180508DF_COLDEN_AVENUE_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 05 2235
- Downstream MH
- 05 2234
- Dir. of Survey
- Downstream
- Length Surveyed
- 2.1 ft.
- Total Length
- 2.1 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 5
- O&M Quick
- 5141
- O&M Rating
- 9
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 05 2235 to 05 2234 Observation photos (7)

0 ft. - Upstream Manhole, Survey Begins - 1:30 PM

0.1 ft. - Water Mark, 100 %of cross sectional area

0.1 ft. - Water Level, 100 %of cross sectional area

2 ft. - General Observation - Grease Throughout The Reach (5%)

2 ft. - Alignment Down, 45 %

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

2.1 ft. - Survey Abandoned - HIGH WATER