Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 15, 2018, 06:33 PM
Date
02/15/2018
W/O
0690350
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00003
PipeID
P00429
Time
10:33 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7633
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
20180215DF_DAVIDSON_CITY_TR_SECTS_1_2_3
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
08 0376
Downstream MH
08 0377
Dir. of Survey
Upstream
Length Surveyed
127 ft.
Total Length
127 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 08 0376 to 08 0377
MH: 08 0376MH: 08 0377upstream0 ft. AMH - Upstream Manhole, Survey Ends - 11:35 AM1.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.9 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Finish1.9 ft. MGO - General Observation - Grease Throughout The Reach (5%)49.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"67.1 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start76.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"103.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"125 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start127 ft. AMH - Downstream Manhole, Survey Begins - 10:42 AM127 ft. MWL - Water Level, 25 %of cross sectional area127 ft. MWM - Water Mark, 30 %of cross sectional area

Observations (12)

DistanceCodeObservation
127AMH11:35 AM
125.1SSS
0AMH10:42 AM
0MWL
23.1TFC
77.2TFA
59.9RFJ
125.1RFJ
50.1TFC
125.1MGOGrease Throughout The Reach (5%)
2SSS
0MWM

Properties (6)

additional_info
PIPE ID ON SCREEN IS WRONG. CORRECT ID # IS (P00429)
custom_field_two
3
customer
LACSD
datetime
2018-02-15T10:33:14-08:00
documentation
FRANKLIN, IGNACIO
is_lateral_inspection
false