Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 19, 2021, 10:00 AM
  • 05 0562_05 0561_01192021_021727.mp4

Date
01/19/2021
W/O
865324
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00460
PipeID
P05781
Time
2:00 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8424
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
02
Purpose
Routine Assessment
Project
WO_865324_TV05047_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
10 in.
Upstream MH
05 0561
Downstream MH
05 0562
Dir. of Survey
Upstream
Length Surveyed
320.6 ft.
Total Length
320.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312M
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
142
Pipe schematic from manhole 05 0561 to 05 0562
MH: 05 0561MH: 05 0562upstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Ends - 05 05622 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN25.9 ft. RFJ - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YESR - 15% ROOTS25.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 80% ROOTS-LATERAL/OPEN72.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 10% ROOTS-LATERAL/OPEN99.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 65% ROOTS-LATERAL/OPEN120.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN167.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN177 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6" - 85% ROOTS-LATERAL/OPEN215.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - SLEEVE/CONN OFFSET/OPEN223.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN265.8 ft. RML - Roots Medium Lateral, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES265.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 30% ROOTS-LATERAL/OPEN270.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 90% ROOTS-LATERAL/OPEN318.6 ft. MLC - Lining Change, Cured in place318.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start320.6 ft. MWL - Water Level, 25 %of cross sectional area320.6 ft. AMH - Downstream Manhole, Survey Begins - 05 0561320.6 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (4)

  • Lining Change, Cured in place

    2 ft. - Lining Change, Cured in place

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES

    54.8 ft. - Roots Medium Lateral, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YESR - 15% ROOTS

    294.7 ft. - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YESR - 15% ROOTS

Observations (21)

DistanceCodeObservation
318.6DAGS
54.8RML
104.9TFDSLEEVE/CONN OFFSET/OPEN
221.2TFD65% ROOTS-LATERAL/OPEN
294.7RFJ15% ROOTS
0MWL
320.6MGOROACHES @ MH
320.6AMH05 0562
294.7TFD80% ROOTS-LATERAL/OPEN
152.7TFOPEN
200.3TFOPEN
314.6TFOPEN
2MLC
143.6TFD85% ROOTS-LATERAL/OPEN
0AMH05 0561
54.8TFD30% ROOTS-LATERAL/OPEN
96.8TFOPEN
247.8TF10% ROOTS-LATERAL/OPEN
0MWM
49.7TFD90% ROOTS-LATERAL/OPEN
2DAGS

Properties (7)

additional_info
630069011821201
custom_field_two
4
customer
1
datetime
2021-01-19T02:00:02-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP