Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2021, 09:27 AM
  • 05 0556_05 0555_01202021_021922.mp4

Date
01/20/2021
W/O
865324
Weather
Dry
Operator/Surveyor
E. RUIZ
Sewer ID
Z00460
PipeID
P05775
Time
1:27 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7778
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_865324_TV05047_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
27 in.
Upstream MH
05 0556
Downstream MH
05 0555
Dir. of Survey
Downstream
Length Surveyed
214.2 ft.
Total Length
214.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G00
O&M Rating
84
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 05 0556 to 05 0555
MH: 05 0556MH: 05 0555downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 05562 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start212 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish214.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0555

Observations (6)

DistanceCodeObservation
214.2AMH05 0555
0MWM
0MWL
212DAGS
2DAGS
0AMH05 0556

Properties (7)

custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-20T01:27:30-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP