Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 21, 2021, 10:49 AM
  • 05 0550_05 0549_01212021_031218.mp4

Date
01/21/2021
W/O
865324
Weather
Dry
Operator/Surveyor
E. RUIZ
Sewer ID
Z00460
PipeID
P05769
Time
2:49 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7779
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_865324_TV05047_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
27 in.
Upstream MH
05 0550
Downstream MH
05 0549
Dir. of Survey
Downstream
Length Surveyed
231.4 ft.
Total Length
231.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
2
Overall Quick
Overall Rating
98
Pipe schematic from manhole 05 0550 to 05 0549
MH: 05 0550MH: 05 0549downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 05500 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 75" - 85% ROOTS-LATERAL/OPEN29.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 25"29.5 ft. RTL - Roots Tap Lateral, at 10 o'clock, 15 %, within 8 inches of joint: YES75 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN77.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN119.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN121.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN163.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - 65% GREASE-LATERAL/UNKNOWN166.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"208.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN218 ft. MWL - Water Level, 30 %of cross sectional area226.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN229 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish230.6 ft. MGO - General Observation - CORRODED TROUGH231.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0549

Observation photos (3)

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 75" - 85% ROOTS-LATERAL/OPEN

    27.3 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 75" - 85% ROOTS-LATERAL/OPEN

  • Water Level, 30 %of cross sectional area

    218 ft. - Water Level, 30 %of cross sectional area

  • General Observation - CORRODED TROUGH

    230.6 ft. - General Observation - CORRODED TROUGH

Observations (19)

DistanceCodeObservation
231.4AMH05 0549
75TFOPEN
121.9TFOPEN
29.5TFD
226.5TFOPEN
0AMH05 0550
0MWL
77.4TFOPEN
166.6TFA
29.5RTL
208.7TFOPEN
27.3TFD85% ROOTS-LATERAL/OPEN
2DAGS
230.6MGOCORRODED TROUGH
0MWM
229DAGS
218MWL
119.2TFOPEN
163.9TFD65% GREASE-LATERAL/UNKNOWN

Properties (7)

custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-21T02:49:54-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP