Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 21, 2021, 11:15 AM
  • 05 0549_05 0548_01212021_034043.mp4

Date
01/21/2021
W/O
865324
Weather
Dry
Operator/Surveyor
E. RUIZ
Sewer ID
Z00460
PipeID
P05768
Time
3:15 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7779
Sewer Name
05 INGLEWOOD TRUNK #2
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_865324_TV05047_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
30 in.
Upstream MH
05 0549
Downstream MH
05 0548
Dir. of Survey
Downstream
Length Surveyed
350.8 ft.
Total Length
350.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312N
O&M Rating
149
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 05 0549 to 05 0548
MH: 05 0549MH: 05 0548downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 05492 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - 15% ROOTS IN LATERAL42.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN59.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN99.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"107.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN147.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN148.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"193.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN202.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"211.4 ft. RMC - Roots Medium Connection, from 10 to 02 o'clock, 10 %, within 8 inches of joint: NO253.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"306.2 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6" - 10% ROOTS-LATERAL/ACTIVE311.4 ft. TFD - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: NO, 6" - 65% ROOTS-LATERAL/ACTIVE335.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - 15% ROOTS-LATERAL/OPEN348 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0548350.8 ft. MGO - General Observation - ROACHES @ MH

Observation photos (3)

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - 15% ROOTS IN LATERAL

    18.3 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - 15% ROOTS IN LATERAL

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"

    211.4 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"

  • General Observation - ROACHES @ MH

    350.8 ft. - General Observation - ROACHES @ MH

Observations (22)

DistanceCodeObservation
0MWL
99.1TFA
193.8TFOPEN
311.4TFD65% ROOTS-LATERAL/ACTIVE
0MWM
0AMH05 0549
59.9TFOPEN
350.8AMH05 0548
107.5TFOPEN
211.4TFA
253.9TFA
42.4TFOPEN
335.5TFD15% ROOTS-LATERAL/OPEN
147.5TFOPEN
18.3TFD15% ROOTS IN LATERAL
2DAGS
306.2TFD10% ROOTS-LATERAL/ACTIVE
348DAGS
148.4TFA
202.9TFOPEN
350.8MGOROACHES @ MH
211.4RMC

Properties (7)

custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-21T03:15:31-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP