Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 15, 2021, 05:44 AM
  • F 0271_F 0270_01142021_222057.mp4

Date
01/14/2021
W/O
865108
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00040
PipeID
P10224
Time
9:44 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8422
Sewer Name
F JOINT OUTFALL F - UNIT 4 RELIEF
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_865108_TV02204_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
15 in.
Upstream MH
F 0271
Downstream MH
F 0270
Dir. of Survey
Downstream
Length Surveyed
806.5 ft.
Total Length
806.5 ft.
Structural Index
3
Structural Quick
593_
Structural Rating
847
O&M Index
2
O&M Quick
412x
O&M Rating
572
Overall Index
2
Overall Quick
Overall Rating
1419
Pipe schematic from manhole F 0271 to F 0270
MH: F 0271MH: F 0270downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02710 ft. MWL - Water Level, 25 %of cross sectional area0.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start19.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start64.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish183.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS802.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish802.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish802.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish802.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish806.5 ft. AMH - Downstream Manhole, Survey Ends - F 0270806.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    0.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    806.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
0MWM
802.7SSS
802.7SAP
0AMHF 0271
802.7DSZ
806.5AMHF 0270
0MWL
183.1DSZDEBRIS
0.1SSS
2SAP
19.2SRV
64.9SRV
802.7DAGS
806.5MGOCOCKROACHES IN MANHOLE
2DAGS

Properties (8)

additional_info
630069011421201
custom_field_three
SURFC. REINFRCMNT. VISIBLE, SURFC. AGG. PROJECTING
custom_field_two
2
customer
1
datetime
2021-01-14T21:44:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31219