Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2021, 11:42 AM
  • 03 0609_C 0070_01052021_040814.mp4

Date
01/05/2021
W/O
859944
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00389
PipeID
P05254
Time
3:42 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8347
Sewer Name
03 NORTH LONG BEACH RELIEF TRUNK
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_859944_TV03113_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
15 in.
Upstream MH
03 0609
Downstream MH
C 0070
Dir. of Survey
Downstream
Length Surveyed
68.6 ft.
Total Length
68.6 ft.
Structural Index
3
Structural Quick
5B3B
Structural Rating
136
O&M Index
3
O&M Quick
5141
O&M Rating
42
Overall Index
3
Overall Quick
Overall Rating
178
Pipe schematic from manhole 03 0609 to C 0070
MH: 03 0609MH: C 0070downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 06092.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - REINFORCEMENT VISIBLE & MISSING THROUGHOUT2.1 ft. IG - Infiltration Gusher, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLY INFILTRATION @ A JOINT - MINERAL / CRYSTALS BUILD-UP OBSERVED17 ft. ID - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES, Start17 ft. H - Hole, at 12 o'clock, within 8 inches of joint: NO21 ft. H - Hole, at 12 o'clock, within 8 inches of joint: NO46.8 ft. MGO - General Observation - LARGE HOLE / THIN SEWER CEILING - 11 TO 1 O'CLOCK68.6 ft. MSA - Survey Abandoned - CAM BLKD BY 20% GREASE68.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish68.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish68.6 ft. ID - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish68.6 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO68.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Gusher, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLY INFILTRATION @ A JOINT - MINERAL / CRYSTALS BUILD-UP OBSERVED

    2.1 ft. - Infiltration Gusher, from 11 to 01 o'clock, within 8 inches of joint: NO - POSSIBLY INFILTRATION @ A JOINT - MINERAL / CRYSTALS BUILD-UP OBSERVED

  • Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    17 ft. - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 12 o'clock, within 8 inches of joint: NO

    17 ft. - Hole, at 12 o'clock, within 8 inches of joint: NO

  • Hole, at 12 o'clock, within 8 inches of joint: NO

    21 ft. - Hole, at 12 o'clock, within 8 inches of joint: NO

  • Survey Abandoned - CAM BLKD BY 20% GREASE

    68.6 ft. - Survey Abandoned - CAM BLKD BY 20% GREASE

  • Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: NO

    68.6 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
2.1SRV
0MWL
68.6MSACAM BLKD BY 20% GREASE
2.1SSS
2.1SAP
2.1MGOREINFORCEMENT VISIBLE & MISSING THROUGHOUT
17ID
68.6SRV
17H
68.6SAP
0MWM
2.1IGPOSSIBLY INFILTRATION @ A JOINT - MINERAL / CRYSTALS BUILD-UP OBSERVED
46.8MGOLARGE HOLE / THIN SEWER CEILING - 11 TO 1 O'CLOCK
21H
0AMH03 0609
68.6ID
68.6DAGS
68.6SSS

Properties (7)

additional_info
630075010421203
custom_field_three
MULTPL.HOLES/REINFORCMNT.VISBL.& MISNG./INFLTRTIN.
custom_field_two
5
customer
1
datetime
2021-01-05T03:42:35-08:00
documentation
PROPIPE
is_lateral_inspection
false