- Date
- 02/01/2021
- W/O
- 0870251
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00691
- PipeID
- P14306
- Time
- 1:30 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1711
- Sewer Name
- 18 NORTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 15
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210126MDM_NORTH_PLANT_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 18 0454
- Downstream MH
- 18 0036
- Dir. of Survey
- Downstream
- Length Surveyed
- 101.7 ft.
- Total Length
- 101.7 ft.
- Structural Index
- 2
- Structural Quick
- 3A2B
- Structural Rating
- 64
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 68
Pipe schematic from manhole 18 0454 to 18 0036 Observation photos (4)

65.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

82.8 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT

88.4 ft. - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL

101.1 ft. - General Observation - DOWNSTREAM STOPLOG IN PLACE