Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2021, 10:03 AM
  • 22 0788_22 0787A_01112021_021746.mp4

Date
01/11/2021
W/O
865110
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00824
PipeID
P17153
Time
2:03 AM
Certificate
U-115-06002794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8371
Sewer Name
22 RAMONA AVENUE TRUNK
City
LA VERNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_865110_TV22089_DEC2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0788
Downstream MH
22 0787A
Dir. of Survey
Downstream
Length Surveyed
233.3 ft.
Total Length
233.3 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 22 0788 to 22 0787A
MH: 22 0788MH: 22 0787Adownstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 07880 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"50.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"54 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"55.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start56.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES121.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"125.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"197.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"201.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8", 8"230.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish230.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish233.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0787A233.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"

    12.5 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    55.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    56.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
2MGOMAG COAT
121.5TF
233.3AMH22 0787A
0MWM
56.5FM
233.3MGOCONNECTION AT MH 9 O'CLOCK
197.5TF
0AMH22 0788
50.2TF
125.6TFC
12.5TB
2SAP
230.3DAGS
0MWL
54TFC
55.6DAGS
201.3TFC
230.3SAP

Properties (6)

custom_field_three
AGGREGATE PROJECTING, FRACTURES
custom_field_two
2
customer
1
datetime
2021-01-11T02:03:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false