Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2021, 10:52 AM
  • 22 0786_22 0785_01112021_031414.mp4

Date
01/11/2021
W/O
865110
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00824
PipeID
P17150
Time
2:52 AM
Certificate
U-115-06002794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8371
Sewer Name
22 RAMONA AVENUE TRUNK
City
LA VERNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_865110_TV22089_DEC2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0786
Downstream MH
22 0785
Dir. of Survey
Downstream
Length Surveyed
345.4 ft.
Total Length
345.4 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0786 to 22 0785
MH: 22 0786MH: 22 0785downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 07860 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"122.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"209.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"247.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES265.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"342.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0785

Observation photos (3)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    247.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
345.4AMH22 0785
0AMH22 0786
247.9FM
0MWM
209.8TF
0MWL
342.2SAP
2MGOMAG COAT
2SAP
79TF
265.1TF
122.6TF

Properties (6)

custom_field_three
AGGREGATE PROJECTING, FRACTURE
custom_field_two
2
customer
1
datetime
2021-01-11T02:52:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false