Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2021, 03:43 PM
  • 29 0232_29 0063A_01042021_080545.mp4

Date
01/04/2021
W/O
865165
Weather
Dry
Operator/Surveyor
N..ZAHREDDINE
Sewer ID
Z01015
PipeID
P24135
Time
7:43 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8091
Sewer Name
29 EASTSIDE INTERCEPTOR SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_865165_TV29080_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0232
Downstream MH
29 0063A
Dir. of Survey
Downstream
Length Surveyed
165.7 ft.
Total Length
165.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
54
Pipe schematic from manhole 29 0232 to 29 0063A
MH: 29 0232MH: 29 0063Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02320 ft. MWL - Water Level, 5 %of cross sectional area8.9 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"27.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start70.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.9 ft. MMC - Material Change, Cast Iron - START OF CAST IRON PIPING105 ft. MGO - General Observation - END OF THIS CAST IRON PIPING151.2 ft. MMC - Material Change, Cast Iron - 2ND START - CAST IRON PIPING163 ft. MGO - General Observation - END OF 2ND CAST IRON PIPING164.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish165.7 ft. AOC - Drop Connection, Survey Ends - 29 0063A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    27.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Material Change, Cast Iron - START OF CAST IRON PIPING

    94.9 ft. - Material Change, Cast Iron - START OF CAST IRON PIPING

  • Material Change, Cast Iron - 2ND START - CAST IRON PIPING

    151.2 ft. - Material Change, Cast Iron - 2ND START - CAST IRON PIPING

Observations (13)

DistanceCodeObservation
0MWM
0AMH29 0232
151.2MMC2ND START - CAST IRON PIPING
27.4DAGS
105MGOEND OF THIS CAST IRON PIPING
163MGOEND OF 2ND CAST IRON PIPING
165.7AOC29 0063A
94.9MMCSTART OF CAST IRON PIPING
72.6TFA
164.2DAGS
0MWL
70.6TFA
8.9TFA

Properties (7)

additional_info
630138010421061
custom_field_three
GREASE
custom_field_two
4
customer
1
datetime
2021-01-04T07:43:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false