- Date
- 01/11/2021
- W/O
- 865210
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z01172
- PipeID
- P04252
- Time
- 4:13 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8414
- Sewer Name
- 02 DOUGLAS AVENUE RELOCATION TRUNK
- City
- EAST LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- RFIR_WO_865210_TV02250_DEC2020
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 8 in.
- Width
- 8 in.
- Upstream MH
- 02 1887
- Downstream MH
- 02 1888
- Dir. of Survey
- Upstream
- Length Surveyed
- 74.8 ft.
- Total Length
- 74.8 ft.
- Structural Index
- 3
- Structural Quick
- 493B
- Structural Rating
- 78
- O&M Index
- 2
- O&M Quick
- 312B
- O&M Rating
- 33
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 111
Pipe schematic from manhole 02 1887 to 02 1888 Observation photos (6)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

32.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

51.6 ft. - Repair Other, within 8 inches of joint: YES - LINK PIPE

53.8 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

72.1 ft. - Repair Other Defective, within 8 inches of joint: YES - MISSHAPED