Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2021, 09:14 AM
  • 16 0514_16 0513_01122021_013007.mp4

Date
01/12/2021
W/O
865111
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00659
PipeID
P13565
Time
1:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8416
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_865111_TV16119_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0514
Downstream MH
16 0513
Dir. of Survey
Downstream
Length Surveyed
278.8 ft.
Total Length
278.8 ft.
Structural Index
3
Structural Quick
4E3C
Structural Rating
192
O&M Index
2
O&M Quick
2J11
O&M Rating
111
Overall Index
3
Overall Quick
Overall Rating
303
Pipe schematic from manhole 16 0514 to 16 0513
MH: 16 0514MH: 16 0513downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05132 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start18.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start40.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start61.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish61.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish61.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"101 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"120.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"161.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"181.9 ft. RFC - Roots Fine Connection, from 01 to 05 o'clock, within 8 inches of joint: YES181.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish222.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start222.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"242.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"276.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish276.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish278.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE278.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0513

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    11.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    61.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 01 to 05 o'clock, within 8 inches of joint: YES

    181.9 ft. - Roots Fine Connection, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    222.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    278.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (24)

DistanceCodeObservation
61.3FM
181.9RFC
61.3CL
242.3TBA
61.3CM
161.3TBA
276.2CM
61.3TBA
40.7TBA
222.3CM
222.3TBA
2DAGS
278.8MGOCOCKROACHES IN MANHOLE
278.8AMH16 0513
0MWM
11.4CL
181.9TBA
276.2DAGS
18.3CM
101TBA
120.7TBA
0MWL
0AMH16 0513
200.6FM

Properties (7)

additional_info
630069011121202
custom_field_three
FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2021-01-12T01:14:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false