- Date
- 01/22/2021
- W/O
- 087025
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00691
- PipeID
- P14343
- Time
- 1:46 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1702
- Sewer Name
- 18 NORTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 14
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210121MDM_NORTH_PLANT_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 16 in.
- Upstream MH
- 18 0488
- Downstream MH
- 18 0489
- Dir. of Survey
- Upstream
- Length Surveyed
- 40.9 ft.
- Total Length
- 40.9 ft.
- Structural Index
- 4
- Structural Quick
- 5121
- Structural Rating
- 7
- O&M Index
- 5
- O&M Quick
- 5141
- O&M Rating
- 9
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 16
Pipe schematic from manhole 18 0488 to 18 0489 Observation photos (4)

40.8 ft. - General Photograph - BROKEN PIPE

40.8 ft. - Deposits Settled Other, 60 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - POSSIBLE BROKEN PIPE

40.8 ft. - Broken, from 06 to 10 o'clock, within 8 inches of joint: YES

40.9 ft. - Downstream Manhole, Survey Ends(COMPLETED BY REVERSE INSPECTION) - 2:45AM(COMPELETED BY REVERSE INSPECTION)