Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2021, 08:35 AM
  • 18 0489_18 0488_1212021_041220.mp4

Date
01/22/2021
W/O
087025
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14343
Time
12:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1702
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20210121MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0489
Downstream MH
18 0488
Dir. of Survey
Downstream
Length Surveyed
295.4 ft.
Total Length
295.4 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
83
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
83
Pipe schematic from manhole 18 0489 to 18 0488
MH: 18 0489MH: 18 0488downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM2.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT4.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - S7.7 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SLIGHT12.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL17.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL25.6 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL25.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL25.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE28.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H28.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - H35.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H41.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H41.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H54 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H54 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H56.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H59.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H67.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL71.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Active80.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL122 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H124.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H127.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H134.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL137.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H140.1 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - H141.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active145.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - OUTER SURFACE CORRISON148.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - OUER SURFACE CORRISON166.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H176.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H177.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Open194.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H219.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H222.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H224.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H227.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open242.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL242.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL248 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H264.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL267.1 ft. MWL - Water Level, 40 %of cross sectional area282.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H285.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H286.4 ft. MWL - Water Level, 80 %of cross sectional area295 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H295 ft. B - Broken, from 03 to 06 o'clock, within 8 inches of joint: YES - WITH OF PIPE INTRUDING IN OUR LINE295.4 ft. MSA - Survey Abandoned - POSSIBLE BROKEN PIPE UNDER FLOW

Observation photos (5)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    67.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - OUTER SURFACE CORRISON

    145.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - OUTER SURFACE CORRISON

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    242.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Broken, from 03 to 06 o'clock, within 8 inches of joint: YES - WITH OF PIPE INTRUDING IN OUR LINE

    295 ft. - Broken, from 03 to 06 o'clock, within 8 inches of joint: YES - WITH OF PIPE INTRUDING IN OUR LINE

  • Survey Abandoned - POSSIBLE BROKEN PIPE UNDER FLOW

    295.4 ft. - Survey Abandoned - POSSIBLE BROKEN PIPE UNDER FLOW

Observations (52)

DistanceCodeObservation
242.4FCSL
141.5TFActive
295FCH
80.4FLSL
25.6FCSL
67.4FLSL
264.9FLSL
56.5FCH
134.7FCSL
0MWL
295BWITH OF PIPE INTRUDING IN OUR LINE
248FCH
28.2FLH
286.4MWL
219.3FLH
41.4FLH
0MWM
224.2FCH
137.3FCH
140.1FCH
71.8TFActive
25.6FCSL
122FLH
145.5SSSOUTER SURFACE CORRISON
25.6FLHAIRLINE
54FCH
282.1FLH
41.4FLH
222.5FLH
2.8FCSLIGHT
17.8FCSL
35.7FCH
242.4FLSL
194.9FLH
227.5TFOpen
148.9SSSOUER SURFACE CORRISON
295.4MSAPOSSIBLE BROKEN PIPE UNDER FLOW
176.7FLH
54FLH
177.4TFOpen
285.4FLH
0MGOConn. @ Mh, 3 O' Clock. Active
4.9FCS
166.8FCH
28.2FMH
59.3FCH
127.1FCH
0AMH12:35AM
7.7FCSLIGHT
124.7FCH
267.1MWL
12.8FCSL

Properties (6)

custom_field_three
BROKEN PIPE 294' DOWNSTTREAM
custom_field_two
1
customer
LACSD
datetime
2021-01-22T00:35:00-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false