- Date
- 01/21/2021
- W/O
- 0870120
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00275
- PipeID
- P04134
- Time
- 12:31 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1701
- Sewer Name
- 02 INDIANA STREET RELIEF TRUNK
- City
- LOS ANGLES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 07A
- Purpose
- Routine Assessment
- Project
- 20210121MDM_INDIANA_STREET_RELIEF_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 11.09000015258789 in.
- Upstream MH
- 02 1784
- Downstream MH
- 02 1783
- Dir. of Survey
- Downstream
- Length Surveyed
- 634.8 ft.
- Total Length
- 634.8 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 4
- O&M Quick
- 5142
- O&M Rating
- 13
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 16
Pipe schematic from manhole 02 1784 to 02 1783 Observation photos (5)

90.5 ft. - Deposits Attached Grease, 40 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO, Start

102.3 ft. - Deposits Attached Grease, 25 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

124.9 ft. - Camera Underwater, Start

192.1 ft. - Water Level, 5 %of cross sectional area

634.3 ft. - Lining Failure Other, from 07 to 06 o'clock, within 8 inches of joint: NO - ROUGH OUTHER SUFACE ON LINER THROUGHOUT REACH