Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2021, 07:14 AM
  • H 1532_H 1531_01052021_233806.mp4

Date
01/05/2021
W/O
865004
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01205
PipeID
P26032
Time
11:14 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8367
Sewer Name
H JOINT OUTFALL H - UNIT 8N RELIEF
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
25
Purpose
Routine Assessment
Project
WO_865004_TV22093_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1532
Downstream MH
H 1531
Dir. of Survey
Downstream
Length Surveyed
482.8 ft.
Total Length
482.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 1532 to H 1531
MH: H 1532MH: H 1531downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 15323 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start480.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish482.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK482.8 ft. AMH - Downstream Manhole, Survey Ends - H 1531

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWL
482.6MGOCONNECTION AT MH 3 O'CLOCK
480.3DAGS
3DAGS
482.8AMHH 1531
0MWM
0AMHH 1532

Properties (7)

custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-05T23:14:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39969