Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2021, 11:07 AM
  • H 1520_H 1519_01122021_032450.mp4

Date
01/12/2021
W/O
865004
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01205
PipeID
P26020
Time
3:07 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8374
Sewer Name
H JOINT OUTFALL H - UNIT 8N RELIEF
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
25
Purpose
Routine Assessment
Project
WO_865004_TV22093_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1520
Downstream MH
H 1519
Dir. of Survey
Downstream
Length Surveyed
322.1 ft.
Total Length
322.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 1520 to H 1519
MH: H 1520MH: H 1519downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 15200 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start62.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"319.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish322.1 ft. AMH - Downstream Manhole, Survey Ends - H 1519

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2DAGS
319.2DAGS
322.1AMHH 1519
0AMHH 1520
62.1TF
0MWL
0MWM

Properties (7)

custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
4
customer
1
datetime
2021-01-12T03:07:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39832