Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2021, 05:48 PM
  • 29 0245_29 0058_01042021_102357.mp4

Date
01/04/2021
W/O
864948
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z01015
PipeID
P24148
Time
9:48 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8092
Sewer Name
29 EASTSIDE INTERCEPTOR SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_864948_TV29115_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0245
Downstream MH
29 0058
Dir. of Survey
Downstream
Length Surveyed
311.9 ft.
Total Length
311.9 ft.
Structural Index
2
Structural Quick
4132
Structural Rating
132
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole 29 0245 to 29 0058
MH: 29 0245MH: 29 0058downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 02450 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN40.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4"88.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN90.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN138.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"140.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN188.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN191.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4" - OPEN239.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN242.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN290 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN292.4 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES292.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - CONN BROKEN/OPEN309 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311 ft. MGO - General Observation - ROACHES @ MH311.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0058

Observations (24)

DistanceCodeObservation
2DAGS
292.6TFDCONN BROKEN/OPEN
138.3TFA
90.6TFOPEN
290TFOPEN
191.7TFOPEN
311.9AMH29 0058
2SSS
0AMH29 0245
309SSS
292.4FM
0MWL
311MGOROACHES @ MH
140.8TFOPEN
2CM
242.1TFOPEN
309DAGS
309CM
188.8TFOPEN
0MWM
40.4TFA
88.1TFOPEN
239.8TFOPEN
38.1TFOPEN

Properties (7)

additional_info
630138010421062
custom_field_three
GREASE
custom_field_two
3
customer
1
datetime
2021-01-04T09:48:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false