- Date
- 01/05/2021
- W/O
- 864946
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00703
- PipeID
- P14401
- Time
- 10:25 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8404
- Sewer Name
- 18 SORENSEN AVENUE TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_864946_TV18014_DEC2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 10 in.
- Width
- 10 in.
- Upstream MH
- 18 0551
- Downstream MH
- 18 0550
- Dir. of Survey
- Downstream
- Length Surveyed
- 316.2 ft.
- Total Length
- 316.2 ft.
- Structural Index
- 4
- Structural Quick
- 5141
- Structural Rating
- 15
- O&M Index
- 2
- O&M Quick
- 412K
- O&M Rating
- 128
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 143
Pipe schematic from manhole 18 0551 to 18 0550 Observation photos (6)

0 ft. - General Observation - COCKROACHES IN MANHOLE

2 ft. - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

216.5 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

263.9 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

264.4 ft. - General Photograph - FRACTURES

316.2 ft. - General Observation - COCKROACHES IN MANHOLE