Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2019, 07:52 PM
  • A 0304_A 0303_4302019_131021.mp4

Date
04/30/2019
W/O
0767441
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00325
PipeID
P08214
Time
12:52 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7972
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Capital Improvement Program Assesment
Project
20190425DF_JOA_1A_SAN_JOSE_CREEK_WRP_INT
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0303
Downstream MH
A 0304
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole A 0303 to A 0304
MH: A 0303MH: A 0304upstream0 ft. MSA - Survey Abandoned - HIGH WATER0.1 ft. LU - Alignment Up, 45 %0.1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 50% MAG0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. MGO - General Observation - Grease Throughout The Reach (5%)0.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MWM - Water Mark, 100 %of cross sectional area2.1 ft. AMH - Downstream Manhole, Survey Begins - 12:55 PM2.1 ft. MWL - Water Level, 100 %of cross sectional area

Observation photos (8)

  • Water Mark, 100 %of cross sectional area

    0 ft. - Water Mark, 100 %of cross sectional area

  • Alignment Up, 45 %

    2 ft. - Alignment Up, 45 %

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 50% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 50% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - Grease Throughout The Reach (5%)

    2 ft. - General Observation - Grease Throughout The Reach (5%)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - HIGH WATER

    2.1 ft. - Survey Abandoned - HIGH WATER

Observations (10)

DistanceCodeObservation
0MWM
2LU
2SZ50% MAG
0AMH12:55 PM
2SSS
2MGOGrease Throughout The Reach (5%)
2SAP
2.1MSAHIGH WATER
2SAV
0MWL

Properties (6)

additional_info
VIEF OF THE UPLEG FROM THE D/S SIPHON
custom_field_two
5
customer
LACSD
datetime
2019-04-30T12:52:59-07:00
documentation
FRANKLIN, CASTILLO, BRAR
is_lateral_inspection
false